The values in these tables correspond to a single connection at an ambient of 25 deg C in a stable environment and a maximum temperature of 85 deg C without insulation.
Cross sectional area | Terminal width | Number of braids | Max current plain copper – Amps | Max current tinned copper – Amps |
60 mm2 | 30 mm
40 mm |
1 x 60 | 351
384 |
389
426 |
75 mm2 | 30 mm
40 mm |
1 x 75 | 396
432 |
440
480 |
100 mm2 | 40 mm
50 mm |
1 x 100 | 505
542 |
560
602 |
120 mm2 | 40 mm
50 mm |
1 x 120 | 558
597 |
619
663 |
150 mm2 | 40 mm
50 mm |
1 x 150 | 632
673 |
701
747 |
200 mm2 | 40 mm
50 mm |
2 x 100 | 744
788 |
826
875 |
300 mm2 | 50 mm
60 mm |
3 x 100
2 x 150 |
991
1039 |
1100
1153 |
400 mm2 | 60 mm
80 mm |
2 x 200
4 x 100 |
1222
1323 |
1356
1468 |
500 mm2 | 60 mm
100 mm |
5 x 100 | 1390
1600 |
1542
1775 |
600 mm2 | 60 mm
80 mm |
3 x 200
6 x 100 |
1548
1655 |
1718
1837 |
800 mm2 | 80 mm
100 mm |
4 x 200 | 1950
2066 |
2164
2293 |
1000 mm2 | 80 mm
100 mm |
10 x 100 | 2222
2341 |
2465
2597 |
1200 mm2 | 100 mm
120 mm |
12 x 100
6 x 200 |
2597
2723 |
2882
3021 |
1600 mm2 | 120 mm
150 mm |
8 x 200 | 3202
3468 |
3553
3848 |
2000 mm2 | 120 mm
150 mm |
10 x 200 | 3919
4193 |
4349
4653 |
These values are for guidance only and Tranect Ltd cannot be held liable for any circumstances beyond it’s control.